Sizing a Used Generator for a Wellsite or Camp: Prime vs Standby, Voltage and Fuel

How prime, standby and continuous ratings differ, and what voltage, fuel and load details to confirm before buying a used wellsite or camp generator.

By Redeploy HQ6 minute read · 6 topicsUpdated Nov 15, 2026
In this guide

Buyer checklist

  1. 01

    Overview

    A used generator that is large enough on a nameplate can still be the wrong machine for a wellsite or camp. The rating (prime, standby or continuous), the voltage and the fuel have to match the load and the way the unit will be run. This guide explains those ratings as they are defined in ISO 8528-1, lists the electrical and fuel details to confirm on a used package, and outlines a practical way to size the unit without treating a listing kilowatt figure as the whole answer.

    Browse used generators for sale, including generators in Alberta. Portable light plants are listed separately under light towers.

  2. 02

    Prime, standby and continuous: why the nameplate rating matters

    Generator-set ratings are defined in ISO 8528-1. Manufacturer explanations of that standard, including Caterpillar and Cummins, use the following definitions. Always check the data sheet for the unit you are buying, because some manufacturers publish additional brand-specific ratings.

    ISO 8528-1 also defines other classes, including Limited-Time Running Power. If a used listing only says “350 kW” or “500 kW” with no rating type, ask whether that figure is prime, standby or continuous. A standby number is a higher nameplate than the same machine’s prime number. Sizing a wellsite or camp against a standby figure is a common way to buy a set that will be overloaded in daily service.

    For most wellsite and camp jobs in Western Canada, the generator is the prime or continuous source, not a backup to a utility. Size and compare units on the rating that matches that use.

    • Emergency Standby Power (ESP), often called a standby rating, is the maximum power the set can deliver to a variable load during a utility outage or a test, for up to 200 hours per year. The average load over 24 hours must not exceed 70% of the ESP rating, unless the manufacturer approves otherwise. A standby-rated set is the wrong choice if the generator will be the only power source and will run every day.
    • Prime Power (PRP) is the maximum power the set can deliver to a variable load for an unlimited number of hours per year, with maintenance as prescribed by the manufacturer. The average load over 24 hours must not exceed 70% of the PRP rating, unless the manufacturer approves otherwise. Manufacturer prime ratings often also describe a short-term overload (for example, 10% for a limited number of hours); that overload is a manufacturer condition, not a reason to size the set tight.
    • Continuous Power (COP) is the maximum power the set can deliver at a constant load for an unlimited number of hours per year, under the manufacturer’s approved conditions. Continuous is the stricter of the long-running ratings when the load will be steady rather than variable.
  3. 03

    Voltage, phase and frequency

    A used set has to match the voltage, phase and frequency of the load, or you will need transformers and a qualified electrical review. Confirm all of the following on the nameplate and in the seller’s description:

    Canadian industrial sites often use 600 V. Listings also appear at 480 V and at other low-voltage combinations. A 600 V wellsite package is not a drop-in replacement for a 480 V camp, or the reverse, without electrical work. If the listing says “600 V” and you need 480 V, or the set is reconnectable, get that confirmed in writing and reviewed by a qualified electrician.

    Also confirm how the power is taken off the set: a mounted switchgear or breaker, camlocks, a distribution panel, or bare leads. For a camp, ask about the distribution and whether an automatic transfer switch is included (often it is not, and often it is not required if there is no utility). For a wellsite, ask whether the package includes the skid, enclosure, fuel tank, exhaust and any building or walk-in housing.

    • Voltage and whether it is reconnectable
    • Phase (typically three-phase for industrial packages)
    • Frequency (60 Hz in Canada)
    • Power factor used for the kilowatt and kilovolt-ampere ratings
  4. 04

    Fuel, site conditions and starting loads

    Fuel. Diesel packages are the most common used sets. Natural-gas and other gas-fuelled packages also appear, and they have to match the available fuel, gas quality and any site restrictions. Confirm the fuel, the tank capacity if a day tank or skid tank is included, and whether the engine is set up for the fuel you will use. A gas engine on a listing photo is not proof that gas is available at your site.

    Site conditions. Engine and generator ratings assume stated temperature, altitude and intake conditions. A set that is adequate at a low-elevation yard may need to be derated for a higher, hotter site. Ask for the manufacturer’s derating guidance, or have a technician apply it. Do not ignore elevation and summer temperature in Western Canada, especially in the foothills and in northern camps.

    Starting and running load. Add the running kilowatts of the expected load, then consider motor starting and other inrush. Pumps, compressors, HVAC and welders can require a much higher momentary capacity than their running load. A set can be correctly sized for running load and still fail to start the largest motor. If you do not have a load list, build one before you buy: lighting, heat, process motors, pumps, camp services and any intermittent loads, with motor sizes and starting methods where you know them.

    This guide does not offer a rule-of-thumb kilowatt table. The load list and the rating type are the basis for a defensible choice; a salesperson’s “that should be fine” is not.

  5. 05

    What to inspect on a used package

    Ask the seller for:

    Inspect for leaks, damaged radiators or charge-air coolers, worn mounts, damaged switchgear, rodent damage, missing covers, and the condition of the exhaust and enclosure. If you can arrange a start and a loaded run, do so, or require a load-bank test as a condition of the sale. Hours alone do not describe condition; a low-hour set that has sat unused can need as much work as a well-maintained higher-hour set.

    Confirm lifting points and shipping dimensions. Skidded packages often need a picker or a bed truck, and enclosures can be over-height or over-width. See the Alberta oversize and overweight permit rules when the move is in Alberta, and have the carrier confirm permits in any other province on the route.

    • Manufacturer, model, serial numbers, year, and a nameplate photo showing kW, kVA, voltage, hours if displayed, and the rating type
    • Engine and generator end hours, and whether the hour meter is believed to be original
    • Maintenance records, oil analysis, and any rebuild or major repair history
    • A recent load-bank test report, if one exists
    • The fuel type, enclosure type, skid dimensions and weight, and whether the fuel tank, battery, charger and trailer (if any) are included
    • Known faults, leak history and uncompleted repairs
  6. 06

    Buying on Redeploy HQ

    Redeploy HQ lists used and surplus diesel and gas generator packages from Western Canadian sellers. Compare rating type, voltage, fuel, hours and location on the generators page, or narrow to Alberta. If you also need portable lighting, see light towers. For records and identifiers, use Documents for buying used oilfield equipment.

Common questions

Can I run a standby-rated generator as the only power source on a wellsite?

Not if you follow the ISO 8528-1 ESP / standby definition. Standby is for a limited number of hours per year as backup to another source. For a wellsite or camp that will run on the generator every day, compare prime or continuous ratings, not the standby number.

Why is the prime rating lower than the standby rating on the same machine?

They describe different duties. The standby (ESP) figure is a higher, short-duration rating. The prime rating is the figure to use for unlimited annual hours at a variable load, subject to the 24-hour average-load limit in ISO 8528-1.

Is 600 V standard for oilfield generators in Canada?

It is a common Canadian industrial voltage, but it is not the only one. Confirm the nameplate voltage, phase and frequency against your load. Do not assume a used 600 V or 480 V set can be changed without a qualified electrical review.

Should I require a load-bank test?

If the seller has a recent test, ask for the report. If not, a load-bank test is a reasonable condition on a used package, especially if the set has been sitting or the maintenance records are thin.

Does the listing kilowatt figure include the enclosure, tank and switchgear?

Not always. Confirm what is mounted on the skid, the shipping dimensions and weight, and whether switchgear, a tank, a trailer or a building is included in the price.